Alutal Measure & Trust

Mineral Insulated Heat Trace - MI

Chromalox MI mineral insulated heating cables provide rugged and reliable heat tracing for a variety of demanding applications. The high nickel alloy sheath, magnesium oxide dielectric insulation and resistance wire construction allow the tracing of equipment up to 1100°F maintenance temperatures and excellent resistance to many corrosive environments. At lower temperatures, watt densities of up to 50 W/Ft can be designed. Please contact factory for cable maintenance temperature above 400°F.

request quote

The product

WARNING — A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improperly installed. A minimum trip level of 30 mA is recommended to minimize nuisance tripping.

  • Constant Wattage Series Resistance Heating Cable Sets
  • Process Temperature Maintenance to 1100°F (593° C)
  • Maximum Exposure Temp, Power Off, 1200°F (648° C)
  • Corrosion Resistant Alloy 825 or Stainless Steel Sheath
  • Factory Assembled Cable Sets — Ready for Installation
  • Fully Annealed Sheath allows Field Bending
  • Min. Bend Radius = 6 X Cable Diameter
  • For Use on Metal Pipes only
  • Approvals
    Factory Mutual (FM) Approved and CSA certified for ordinary areas. FM and CSA Approved for hazardous (classified) areas.
    CSA and FM Approved:
    • Class I, Div. 1* & 2 Groups A*, B, C, D (gases, vapors)
    • Class II, Div. 1* & 2 Groups E*, F, G (combustible dust)
    • Class III, Div. 2 (easily ignitable fibers and fillings)
    • Consult Chromalox for T ratings
    *CSA Only
    *Stainless steel not 3rd party approved.
    ATEX Approved:
    • II 2 G Ex e II T1 to T6 Gb
    IECEx Approved:
    • Ex IIC T1 to T6 Gb

MI heat trace cable applications

  • Freeze Protection
  • Freeze Protection, High Exposure Temperature
  • Process Maintenance, Low Temperature
  • Process Maintenance, High Temperature

Features of MI Cable
Max. Maintenance Temp. (°F) 900
Max. Exposure Temp. (°F) Power Off 1,100
Max. W/Ft. 80
Max. Circuit Length (Ft.) 500
Buss Wire Size N/A
Voltages Up to 600
Hazardous Ratings Yes
Usable on Plastic Pipe No
Cut-to-Length in Field No
Field Splicable No
Can be Overlapped No
Output Varies with Temp. No
Varies Output Along Length No
Monitor Wire Available No
MI Corrosion Selection Guide
Moisture Yes
Aqueous Solutions of Inorganic Compounds No
Liquids Organic Chemicals Acids or Bases Yes
Acids or Bases No

C – Tin-Plated copper metallic braid for additional protection and ground path
CT
– Fluoropolymer corrosion resistant overjacket over braid for hostile/corrosive environments
CR
– TPR overjacket over braid for protection against certain inorganic chemical solutions