The product
• Input: 4 x 4-20mA analog and 1 digital(24VDC) input allows to the user managing detectors with integrating other equipment to the systems like emergency button.
• Display: Bright and clear LCD display
• Integrity: Easy integration to SCADA systems via Modbus RS485 output
• Relays: 2 Alarm, 1 Fault and AUX adjustable relay contacts. Up to 12 extra relay outputs for specific applications
• Logging: Stores all alarm, fault and maintenance events up 24logs to provide a history of detectors connected
• Monitoring: Continuously monitoring of 4 detector gas concentrations
• Remote Control: Up to 16 S-DP4 control panel can be monitored in one center via Prosense Gas Monitoring software.
• Diversification: Different gases in different measuring ranges(ppm,LEL,VOL) can be connected
• Body: PC(Polycarbonate) superb performance under harsh environmental conditions with IP66 protection class.
• Visual/Audial: Independent Alarm and Fault LED indicators for each detector and buzzer
• Modular: Modular structure allows the user specific installation and provide efficiency during the maintenance.
Specification
Backup Battery Fuse | 2A |
Buzzer | YES |
Programming | User friendly software enables easy programming with 4 buttons on panel door |
Backup Battery | 2x12V 7A/h (Optional) |
Power Supply | 220 VAC +/?10% – 110VAC +/-10% |
Main Power Fuse | 2A |
Software Monitoring | Up to 16 panels can be monitored via Prosense Gas Monitoring software remotely |
LED Indicators | 6 LED indicators for Alarm1, Alarm2, Fault, AUX, Battery and Power LED indicators |
Monitoring | Simultaneously monitoring measurements, alarm and fault status |
Dimensions/Weight | 366x276x186mm / 4.25 KG |
IP Rating | IP66 |
Power Consumption | 27VDC/250mA?4,5W max. without connected detectors |
Relay Outputs | Programmable Fault, Alarm1, Alarm2, AUX contacts Adjustable NO/NC contacts Optional Alarm1, Alarm2 and fault relays for each detector |
Event Logging | Storages Alarm, Fault and maintenance logs up to 24 event |
Input | 4 x Analogue 4-20mA 1 Digital Input |
Display | Graphic LCD 128×64 |
Humidity | 10?95%RH Non-Condensing |
Operating Temperature | -20 |
Mounting | Modular Structure |