The product
With 392°F (200°C) fluoropolymer electrical insulation over-jacketing, CWM has outstanding electrical and thermal properties, and is well suited for most chemically hostile environments.
WARNING — A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improperly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping.
- Uniform Thermal Output, Low Energy Cost
- No Inrush at Any Ambient
- Industrial/Process and Commercial/Construction Applications
- Maximum Exposure Temperature, Power Off, 392°F (200°C)
- Steam Cleanable on Process Equipment Up to 190 PSIG (Power Off)
- 4, 8 and 12 W/Ft.
- 120, 208 – 277 and 480 Volt From Stock
- Approximate Size .30 in. W x .25 in. H
- Minimum Bend Radius 1-1/4 in.
- For Use on Metallic Pipes
- Consult Factory for Use on Plastic Pipes
- Approvals (Depends on specific model)
UL Listed for ordinary areas.
CSA Certified for ordinary and:
• Class I, Div. 2, Groups A, B, C, D
• Class II, Div. 2, Groups F, G. Rated T3 Temperature Class2 (Exception: Cable surface temperature shall not exceed 190°C in Class II, Div. 2, Group F; 165°C in Class II, Div. 2, Group G.).
Features
- Durable, non-aging fluoropolymer jacket ensures long service life and can be used in some hostile environments.
- Flexible, easy to install on most equipment and delivers long-term reliable performance.
- Eliminates the need for oversized wiring or switchgear.
- Accurate temperature, reliable electric heat that can be consistently controlled and easily monitored.
- Safe and rugged.
- Parallel circuitry allows cut-to-length.
- High performance, rated to withstand up to 392°F saturated steam (190 psig) temperature (power off).
- Low profile, uses standard size thermal insulation on piping and process equipment.
CWM heat trace cable applications
- Freeze Protection
- Freeze Protection, High Exposure Temperature
- Process Maintenance, Low Temperature
- Process Maintenance, High Temperature
CWM Heat Trace Cable Features | |
Max. Maintenance Temp. (°F) | 320 |
Max. Exposure Temp. (°F) Power Off | 400 |
Max. W/Ft. | 12 |
Max. Circuit Length (Ft.) | 225 – 900 |
Buss Wire Size | 12 |
Voltages | 120, 208-277, 480 |
Hazardous Ratings | Yes |
Usable on Plastic Pipe | No |
Cut-to-Length in Field | Yes |
Field Splicable | Yes |
Can be Overlapped | No |
Output Varies with Temp. | No |
Varies Output Along Length | No |
Accessories | DL/EL/U |
Monitor Wire Available | Contact Factory |
CWM Corrosion Selection Guide | |
Moisture | C, CT |
Aqueous Solutions of Inorganic Compounds | CT |
Liquids Organic Chemicals Acids or Bases | CT |
Acids or Bases | CT |
C – Tin-Plated copper metallic braid for additional protection and ground path
CT – Fluoropolymer corrosion resistant overjacket over braid for hostile/corrosive environments